HT11 series tower online UPS 1-3kVA - INVT
The INVT HT11 series is online UPS with the most advanced DSP control technology which can protect the sensitive device from utility fail, over/under voltage, surges, transients, spikes and other electrical abnormalities.
HT11 series is online double-conversion UPS with full DSP control technology. With high input and output power factor, self-adjusting output frequency and network management, HT11 is a perfect choice for computers, telecommunication equipment and other sensitive devices.
HT11 series is online double-conversion UPS with full DSP control technology. With high input and output power factor, self-adjusting output frequency and network management, HT11 is a perfect choice for computers, telecommunication equipment and other sensitive devices.
more details
Downloads
Request Offer
Features
Advantages
Industries
F.Fonseca is distributor of INVT in Portugal.
- Wide range of input voltage while input PF>99%;
- Output PF of 0.9,more powerful load capability;
- Full protection of overvoltage, circuit short and over temperature;
- LCD/LED display, monitoring all the operation status;
- Auto fan speed adjust;
- In-built output transformer for TX branch.
Advantages
MODEL | Ⅰ | HT1101S | HT1101L | HT1102S | HT1102L | HT1103S | HT1103L |
Ⅱ | HT1101S-Ⅱ | HT1101L-Ⅱ | HT1102S-Ⅱ | HT1102L-Ⅱ | HT1103S-Ⅱ | HT1103L-Ⅱ | |
Capacity | 1kVA | 2kVA | 3kVA | ||||
Phase | Single phase in, single phase out | ||||||
Input voltage | 110VAC-288VAC | ||||||
100% load@>176VAC; 80% load@>154VAC; 70% load@>132VAC; 50% load@>110VAC |
|||||||
Input PF | ≥0.97 | ||||||
Input frequency | 40Hz~70Hz | ||||||
Output PF | Ⅰ | 0.9 | |||||
Ⅱ | 0.8 | ||||||
Output voltage | 220V/230V/240V | ||||||
Voltage regulation | ± 1 % | ||||||
THDu | ≤2% THD, Linear Load | ||||||
≤ 5.5% THD, none-linear | ≤ 5% THD, none-linear | ≤ 5% THD, none-linear | |||||
Crest ratio | 3:1 | ||||||
Efficiency | 87.0% | 91.0% | 90.0% | ||||
Noise | <43dB@<70%load, <47dB@>70%load |
<45dB@<70%load, <50dB@>70%load |
<45dB@<70%load, <50dB@>70%load |
||||
Overload capability | Inverter | 105%~130%: to bypass after 1 min; 150%: to bypass after 30Sec |
|||||
Battery | 105%~130%:shutdown after 10Sec; 150%:shutdown after 5Sec |
||||||
Battery Voltage | Ⅰ | 36VDC | 72VDC | 96VDC | |||
Ⅱ | 24VDC | 48VDC | 72VDC | ||||
Battery type/number | Ⅰ | 12V/7Ah*3 | External | 12V/7Ah*6 | External | 12V/7Ah*8 | External |
Ⅱ | 12V/7Ah*2 | External | 12V/7Ah*4 | External | 12V/7Ah*6 | External | |
Max charging current | 1A | 8A | 1A | 8A | 1A | 8A | |
Interface | RS232,EPO | ||||||
Optional | Intelligent kits, USB(B type),SNMP, dry contact ,surge protection | ||||||
W*D*H(mm) | Ⅰ | 144*353*222 | 190*374*336 | 190*426*336 | |||
Ⅱ | 144*353*222 | 190*374*336 | 190*374*336 | ||||
Weight(Kg) | Ⅰ | 10.5 | 5 | 21 | 8.5 | 24.5 | 9.5 |
Ⅱ | 10 | 6 | 17 | 11 | 22 | 12 |
Industries
- Airports;
- Commercial spaces;
- Data and communication centers;
- Emergency systems;
- Hospitals;
- Hotels;
- Industrial buildings;
- Office buildings;
- Schools;
- Telecommunications;
- Transport.